• With high response speed and stability
• Measurement accuracy 0.04-0.075%FS
• The max. range ratio can reach to 100:1
• Adopt double overload protection technology
• With strong overload capability, the unidirectional pressure can reach to 25MPa
• The max. static pressure can reach to 25MPa
• Provide standard HART bus communication mode
• Sophisticated self-diagnosis and telecommunication function
• Highlighted LCD with backlight
• Local display screen which can rotate by 360º
• Convenient local zero clearing function
• Convenient local zero point, extreme point setting and calibration function
• Convenient local current loop calibration function
The overal performance is the composition error based on the reference accuracy,
Accuracy index
±0.04-0.075%FS range
Stability
≤±0.2%FS/5 years
(Zero-base range, reference conditions, silicone oil filling liquid, 316 stainless steel isolation diaphragm, 4~20mA
analog output, the digital fine-tuning value is equal to the set point value of range.)
Accuracy
(The reference accuracy includes hysteresis, linear, setting ability and repeatability, which are based on terminal.)
±0.075% range
If the range is less than X
±[0.015+0.05]%

Influence of static pressure
±0.15%/10MPa
Influence of zero point
Can correct the zero position again or conduct pressure zero position transference according to the field installation position etc.
Damping time constant
The total damping time constant is equal to the sum of the damping time constants of amplifier unit and diaphragm capsule. The
damping time constant of amplifier unit is adjustable within the range of 0~100s.
Diaphragm capsule (silicone oil)
Time constant (s) (The time constant can be set according to the actual situation of field and is recommended 1S)
Influence of installation position
The changing of installation position, which is parallel to the surface of diaphragm, will not cause the effect of null shift. If the change
between the installation position and the surface of diaphragm do not exceed 90°, the null shift within 0.4KPa can be corrected by
zero setting without influencing the range.


Environment
-20℃~+70℃ (ordinary)
-40℃~+85℃ (the highest)
Storage
-46℃~110℃
With header: -40℃~85℃
Process
Larger than or equal to the atmosphere, please see the following table